The URCA6 is designed for controllers with
initial polarization of analog input (e.g. EXCEL series). This device converts six digital inputs to
one analog output signal 0 - 10V. Connecting discrete inputs (d1 ÷ d6) to the
ground ( ), generate output voltage according to the formula:
U0= 0.15d1 + 0.3d2 + 0.6d3 +
1.2d4 + 2.4d5 + 4.8d6 [V]
| where for: |
| |
|
x=1 ÷ 6 |
|
dX=0 (terminals are opened) |
|
dX=1 (terminals are closed) |
|
LED diodes indicate states of digital inputs.
|
More information:
(118kB )
|