Sterkrak logo SEQUENTIAL CONTROL DEVICE USS136
Pricelist and terms of trade Size: 3.1MB
Sequential Control Device USS136

The USS136  is functional equivalent of the MCAS6-6 module, which converts analog input signal 0 - 10V to seven discrete output states. Relays have SPST-NO contacts. Built-in signal level detection circuit for input voltage allows force logic states omitting transient states. The hysteresis circuit prevents contacts from "flickering" in switching points. LED diodes indicate output states according to the table:

UWE
rising [V]
UWE
falling [V]
S6 S5 S4 S3 S2 S1
0 0
1,7 1,3
3,2 2,8
4,7 4,3
6,2 5,8
7,7 7,3
9,2 8,8
- opened contacts, LEDs switched-off
- closed contacts, LEDs switched-on

More information:  Datasheet of the USS136 (126kB )